63
Reference Manual
00809-0100-2460, Rev DE
Configuration
October 2018
Configuration
3. Select the Field Port that the device is connected to.
In the standard configuration there are six field bus ports available for the Rosemount 2460 System
Hub. The TRL2 bus is the standard field bus interface for devices connected to a Rosemount 2460
System Hub. See “Connecting to a Rosemount 2460 System Hub” on page 30 for more information.
4. Enter the 2410 Device Address for each Rosemount 2410 Tank Hub that is connected to the system
hub. Note that for 2410 Tank Position 1 the same address will be used for the temperature device and
the tank hub itself. This is handled automatically by TankMaster.
5. Enter the appropriate 2410 Tank Position. All field devices on a certain tank are associated with the
same Tank Position in the tank database of the Rosemount 2410 Tank Hub. For a Rosemount 2410
connected to one tank only, all field devices are configured in Tank Position 1.
See “Single tank with a single Rosemount 2410 Tank Hub” on page 71 for an example of how to
configure a Rosemount 2460 System Hub connected to Rosemount 2410 Tank Hubs with one tank
each.
Use Tank Position 2-10 for the multiple tanks version of the Rosemount 2410 Tank Hub. It has a
database with 10 tank positions that allows the tank hub to serve up to ten tanks. Each row in the tank
database of the Rosemount 2460 System Hub corresponds to a tank position in the database of the
Rosemount 2410 Tank Hub. See “Multiple tanks connected to a single Rosemount 2410 Tank Hub” on
page 73 for an example.
Important! The Tank Database of the Rosemount 2460 System Hub must be properly configured to
match the tank databases of all Rosemount 2410 Tank Hubs connected to the system hub.
6. Enter Level Device Address for devices such as the Rosemount 5900S Radar Level Gauge and other
level gauges supported by the Rosemount 2460 System Hub and the Rosemount 2410 Tank Hub.
7. In case the level gauge is a Rosemount 5900S 2-in-1 version, you will need to configure two level
device addresses for one Rosemount 5900 gauge. See the Rosemount Tank Gauging System
Configuration Manual (Document No. 00809-0300-5100) for a detailed description of how to
configure the tank database for a Rosemount 5900S Radar Level Gauge 2-in-1 version.
8. Enter the Temperature Device Address. For “2410 tank position” 1 the same address is used for the
Rosemount 2410 Tank Hub and the temperature device. The tank hub’s address is automatically
copied to the Temperature Device Address field.
For “2410 Tank Position” 2 to 10 you will have to enter the same temperature device addresses as
configured in the tank database of the Rosemount 2410 Tank Hub. Each tank position must have a
unique address.
Note! The Temp Device Address in the Rosemount 2460’s tank database is referred to as the ATD
Modbus Address in the Rosemount 2410 Tank Hub’s tank database.