Configuration
October 2018
Configuration
Single tank with a single Rosemount 2410 Tank Hub
In this example a Rosemount 2460 System Hub is connected to two tanks each of which has a separate
Rosemount 2410 Tank Hub. Each tank has a Rosemount 5900S Radar Level Gauge Radar Level Gauge, a
Rosemount 2240S Multi-Input Temperature Transmitter, and a Rosemount 2230 Graphical Field Display.
The Modbus address configuration is summarized in Tab le 4 -6 :
Table 4-6. Example of Modbus address configuration for Rosemount 2410 Tank Hubs and
connected devices on two tanks
Figure 4-3. Configuration example of a Rosemount Tank Gauging system with a Rosemount 2460
System Hub connected to two tanks each of which has a Rosemount 2410 Tank Hub
For each tank, the Level Device address in the Tank Database of the Rosemount 2460 System Hub must
be equal to the Level Modbus address in the Rosemount 2410 tank database.
The Temperature Device address in the tank database of the Rosemount 2460 System Hub must be
equal to the ATD Modbus address in the tank database of the Rosemount 2410 Tank Hub.
Tank
Rosemount 2410
Tank Hub
Rosemount 5900S
Level Gauge
ATD (2230, 2240S)
Modbus Address
TK-1
101 1 101
TK-2
102 2 102
Rosemount
2410 Tank Hub
Rosemount 5900S
Level Gauge
Rosemount 2240S
Temperature Transmitter
TK-1
TK-2
Rosemount 2460 System Hub
Rosemount 2230
Field Display
Rosemount 2240S
Temperature Transmitter
Rosemount 5900S
Level Gauge
Rosemount
2410 Tank Hub
Rosemount 2230
Field Display