Proline t-mass I 300 HART Commissioning
Endress+Hauser 95
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Maximum frequency value The Frequency option is
selected in the Operating
mode parameter (→  92)
and a process variable is
selected in the Assign
frequency output parameter
(→  94).
Enter maximum frequency. 0.0 to 10 000.0 Hz
Measuring value at minimum
frequency
The Frequency option is
selected in the Operating
mode parameter (→  92)
and a process variable is
selected in the Assign
frequency output parameter
(→  94).
Enter measured value for
minmum frequency.
Signed floating-point
number
Depends on country
and nominal
diameter
Measuring value at maximum
frequency
The Frequency option is
selected in the Operating
mode parameter (→  92)
and a process variable is
selected in the Assign
frequency output parameter
(→  94).
Enter measured value for
maximum frequency.
Signed floating-point
number
Depends on country
and nominal
diameter
Failure mode The Frequency option is
selected in the Operating
mode parameter (→  92)
and a process variable is
selected in the Assign
frequency output parameter
(→  94).
Define output behavior in
alarm condition.
Actual value
Defined value
0 Hz
Failure frequency The Frequency option is
selected in the Operating
mode parameter (→  92)
and a process variable is
selected in the Assign
frequency output parameter
(→  94).
Enter frequency output value
in alarm condition.
0.0 to 12 500.0 Hz
Invert output signal Invert the output signal. No
Yes
* Visibility depends on order options or device settings