3 Transducer Blocks (transmission blocks) PROline Prosonic Flow 93 FOUNDATION Fieldbus
114 Endress+Hauser
Low Flow Cut Off
- Assign
AUTO - OOS Use this function to assign the switch point for the low flow cut off.
Options:
OFF
VOLUME FLOW
Factory setting:
OFF
Low Flow Cut Off
- On Value
AUTO - OOS Specifies the switch-on point of the low flow cut off. Low flow cut
off is active if the setting is a value not equal to "0".
User input:
5-digit floating-point number
Factory setting:
0.0000
Note!
A flow value of "0" is output via the output value OUT (AI Block)
when the low flow cut off responds. In addition, the status
changes to UNCERTAIN.
The unit used is displayed in the Low Flow Cut Off - Unit
parameter and determined in the System Unit - Volume Flow
parameter, (see Page 110).
Low Flow Cut Off
- Unit
read only Displays the unit for the low flow cut off.
Note!
The unit for the low flow cut off is determined by means of the
System Unit - Volume Flow parameter, (see Page 110).
Low Flow Cut Off
- Off Value
AUTO - OOS Specifies the switch-off point of the low flow cut off. Enter the
switch-off point as a positive hysteresis from the switch-on point.
User input:
0...100%
Factory setting:
50%
Example:
Low Flow Cut Off Assign = VOLUME FLOW
Low Flow Cut Off Off-Value = 50%
Low Flow Cut Off On-Value = 10
Low Flow Cut Off Unit = l/s
This results in an off-value of 15 l/s
(10 l/s + [10 l/s · 0.5] = 15 l/s).
TRANSDUCER_CH1 and TRANSDUCER_CH2 (E+H parameters) /
Base index 1200 and 1300
Parameter Write access
with operating
mode
(MODE_BLK)
Description
F06-53xFFxxx-05-xx-xx-en-000