3 Transducer Blocks (transmission blocks) PROline Prosonic Flow 93 FOUNDATION Fieldbus
124 Endress+Hauser
Sensor Param. -
Sensor
Configuration
AUTO - OOS
Note!
This parameter is not active unless one of the following options
was selected in the “Sensor Param. - Measurement” parameter.
• CLAMP ON
• INSERTION
Use this parameter to select the configuration for the ultrasonic
sensors, e.g. the number of traverses (in the Clamp On version) or
whether single-path or dual-path configuration is present (in the
Insertion version)
The options in this parameter depend on the measurement
method selected in the “Sensor Param. - Measurement”
parameter, (see Page 122).
Options:
(if “CLAMP ON” was selected in the “Sensor Param. -
Measurement” parameter)
NO. TRAVERSE: 1
NO. TRAVERSE: 2
NO. TRAVERSE: 3
NO. TRAVERSE: 4
Options:
(if “INSERTION” was selected in the “Sensor Param. -
Measurement” parameter)
SINGLE PATH
DUAL PATH
Factory setting:
NO. TRAVERSE: 2
Sensor Param. -
Cable Length
AUTO - OOS For selecting the length of the sensor cable.
Options:
LEN. 5m/15 feet
LEN. 10m/30 feet
LEN. 15m/45 feet
LEN. 30m/90 feet
Factory setting:
LEN. 5m/15 feet
Sensor Param. -
Position Sensor
read only
Note!
This parameter is not active unless "CLAMP ON" was selected in
the “Sensor Param. - Measurement” parameter and the number of
traverses in the “Sensor Param. - Sensor Configuration”
parameter is 2 or 4.
Displays the position of both sensors on the rail.
Display:
5-digit number combination
“TRANSDUCER_CH1” and “TRANSDUCER_CH2” (E+H parameters) /
Base index 1200 and 1300
Parameter Write access
with operating
mode
(MODE_BLK)
Description