3 Transducer Blocks (transmission blocks) PROline Prosonic Flow 93 FOUNDATION Fieldbus
122 Endress+Hauser
Liquid Data -
Unit Min. Sound
Velocity Liquid
read only Displays the unit for the minimum liquid sound velocity selected in
the “Liquid Data - Min. Sound Velocity Liquid” parameter.
Note!
The unit is selected in the “System Unit - Sound Velocity”
parameter, see Page 111.
Liquid Data -
Max. Sound
Velocity Liquid
AUTO - OOS Entry of the maximum sound velocity of the liquid.
User input:
Fixed-point number 400...3000
Factory setting:
1800
Note!
The unit used is displayed in the “Liquid Data - Unit Max. Sound
Velocity Liquid” parameter.
Liquid Data -
Unit Max. Sound
Velocity Liquid
read only Displays the unit for the maximum liquid sound velocity selected
in the “Liquid Data - Max. Sound Velocity Liquid” parameter.
Note!
The unit is selected in the “System Unit - Sound Velocity”
parameter, see Page 111.
Sensor Param. -
Measurement
AUTO - OOS For selecting which measurement method should be used.
Options:
OFF
CLAMP ON
INSERTION
Factory setting for channel 1:
CLAMP ON
Factory setting for channel 2:
OFF
Caution!
Although the following options also appear in this parameter, they
can only be selected by means of the local display (see Page 63)
or the configuration and service software FieldTool:
• SOUND VEL. LIQUID (liquid sound velocity)
• SOUND VEL. PIPE (pipe sound velocity)
• WALL THICKNESS
“TRANSDUCER_CH1” and “TRANSDUCER_CH2” (E+H parameters) /
Base index 1200 and 1300
Parameter Write access
with operating
mode
(MODE_BLK)
Description