PROline Prosonic Flow 93 FOUNDATION Fieldbus 3 Transducer Blocks (transmission blocks)
Endress+Hauser 121
Liquid Data -
Temperature
AUTO - OOS Entry of the liquid temperature.
User input:
Fixed-point number -273.15...726.85 °C (0...1000 K)
Factory setting:
20
Note!
The unit used is displayed in the Liquid Data - Unit Temperature
parameter.
Liquid Data -
Unit Temperature
read only Displays the unit for the liquid temperature selected in the Liquid
Data - Temperature parameter.
Note!
The unit is selected in the System Unit - Temperature parameter,
see Page 111.
Liquid Data -
Sound Velocity
Liquid
AUTO - OOS Entry of the sound velocity of the liquid.
Measuring the sound velocity of the liquid
Measurement can be carried out via:
The local display (Sensor Quick Setup), see Page 19.
The configuration and service software FieldTool.
User input:
Fixed-point number 400...3000
Factory setting:
1487
Note!
The unit used is displayed in the Liquid Data - Unit Sound
Velocity Liquid parameter.
Liquid Data -
Unit Sound
Velocity Liquid
read only Displays the unit for the liquid sound velocity selected in the
Liquid Data - Sound Velocity Liquid parameter.
Note!
The unit is selected in the System Unit - Sound Velocity
parameter, see Page 111.
Liquid Data -
Min. Sound
Velocity Liquid
AUTO - OOS Entry of the minimum sound velocity of the liquid.
User input:
Fixed-point number 400...3000
Factory setting:
800
Note!
The unit used is displayed in the Liquid Data - Unit Min. Sound
Velocity Liquid parameter.
TRANSDUCER_CH1 and TRANSDUCER_CH2 (E+H parameters) /
Base index 1200 and 1300
Parameter Write access
with operating
mode
(MODE_BLK)
Description