3 Transducer Blocks (transmission blocks) PROline Prosonic Flow 93 FOUNDATION Fieldbus
128 Endress+Hauser
Simulation -
Measurand
AUTO - OOS For activating the simulation for the volume flow.
Options:
OFF
VOLUME FLOW
Factory setting:
OFF
Caution!
The measuring device cannot be used for measuring while this
simulation is in progress.
The simulation functions independently of the position of the
relevant jumpers on the I/O board, (see Operating Instructions
for PROline Prosonic Flow 93 FOUNDATION Fieldbus,
BA078D/06/en, Section 5.4).
The setting is not saved if the power supply fails.
Note!
Active simulation is relayed to downstream function blocks or
higher-level process control systems by means of the status
UNCERTAIN for the output value OUT (AI Block).
Simulation -
Value Measurand
AUTO - OOS This parameter can be used to specify a selectable value (e.g.
12 m
3
/s). This is used to test the assigned parameters in the
flowmeter itself and downstream function blocks.
User input:
5-digit floating-point number
Factory setting:
0
Note!
The unit used is displayed in the Simulation - Unit parameter.
Caution!
The setting is not saved if the power supply fails.
Simulation - Unit read only Displays the unit used in the Simulation - Value Measurand
parameter.
Note!
The unit is taken from the System Unit - Volume Flow parameter,
(see Page 110).
Amp. Device
Family
read only This parameter is only used in the event of servicing.
TRANSDUCER_CH1 and TRANSDUCER_CH2 (E+H parameters) /
Base index 1200 and 1300
Parameter Write access
with operating
mode
(MODE_BLK)
Description