PROline Prosonic Flow 93 FOUNDATION Fieldbus 3 Transducer Blocks (transmission blocks)
Endress+Hauser 127
Calibration Data -
Unit Deviation
Sensor Distance
read only Displays the unit used for the entry in the “Calibration Data -
Deviation Sensor Distance” parameter.
Note!
The unit is selected in the “System Unit - Length” parameter, see
Page 112.
Calibration Data -
Deviation ARC
Length
AUTO - OOS
Note!
This parameter is not active unless "INSERTION" was selected in
the “Sensor Param. - Measurement” parameter and "DUAL PATH"
was selected in the “Sensor Param. - Sensor Configuration”
parameter.
Entry of the arc length deviation.
User input:
5-digit floating-point number
Factory setting:
0
Note!
The unit used is displayed in the “Calibration Data - Unit Deviation
ARC Length” parameter.
Calibration Data -
Unit Deviation
ARC Length
read only Displays the unit used for the entry in the “Calibration Data -
Deviation ARC Length” parameter.
Note!
The unit is selected in the “System Unit - Length” parameter, see
Page 112.
Calibration Data -
Deviation Path
Length
AUTO - OOS
Note!
This parameter is not active unless "INSERTION" was selected in
the “Sensor Param. - Measurement” parameter.
Entry of the path length deviation.
User input:
5-digit floating-point number
Factory setting:
0
Note!
The unit used is displayed in the “Calibration Data - Unit Deviation
Path Length” parameter.
Calibration Data -
Unit Deviation
Path Length
read only Displays the unit used for the entry in the “Calibration Data -
Deviation Path Length” parameter.
Note!
The unit is selected in the “System Unit - Length” parameter, see
Page 112.
“TRANSDUCER_CH1” and “TRANSDUCER_CH2” (E+H parameters) /
Base index 1200 and 1300
Parameter Write access
with operating
mode
(MODE_BLK)
Description