3 Transducer Blocks (transmission blocks) PROline Prosonic Flow 93 FOUNDATION Fieldbus
112 Endress+Hauser
System Unit -
Viscosity
AUTO - OOS For selecting the unit for the viscosity of the fluid.
Options:
mm²/s
cSt
St
Factory setting:
mm²/s
System Unit -
Length
AUTO - OOS For selecting the unit for the measure of length.
The unit you select here is valid for:
Nominal diameter
Diameter
Wall thickness
Liner thickness
Path length
Wire length
Sensor distance
Options:
MILLIMETER
INCH
Factory setting:
Depends on country (MILLIMETER or INCH),
see factory setting Page 76 ff..
System Param. -
Installation
Direction
Sensor
AUTO - OOS This parameter can be used to reverse the sign of the flow rate
variable, if necessary.
Options:
NORMAL (FORWARD)
INVERSE (REVERSE)
Factory setting:
NORMAL (FORWARD)
System Param. -
Flow Damping
AUTO - OOS
Note!
System damping acts on all functions of the measuring device.
Specifies the filter depth of the digital filter.
This reduces the sensitivity of the measuring signal to interference
peaks (e.g. high solids content, gas bubbles in the fluid, etc.). The
measuring system reaction time increases with the filter setting.
The damping acts on all parameters and all downstream function
blocks.
User input:
0...100 s
Factory setting:
0 s
TRANSDUCER_CH1 and TRANSDUCER_CH2 (E+H parameters) /
Base index 1200 and 1300
Parameter Write access
with operating
mode
(MODE_BLK)
Description