3 Transducer Blocks (transmission blocks) PROline Prosonic Flow 93 FOUNDATION Fieldbus
150 Endress+Hauser
Totalizer 1 -
Assign
AUTO - OOS For assigning a measured variable to the totalizer.
Options:
OFF
VOLUME FLOW CH1
VOLUME FLOW CH2
VOLUME FLOW AVERAGE
VOLUME FLOW SUM
VOLUME FLOW DIFF.
Factory setting:
VOLUME FLOW CH1
Note!
The totalizer is reset to 0 as soon as the selection is changed.
Totalizer 1 -
Mode
AUTO - OOS Use this parameter to define how the flow components are to be
totalled by the totalizer.
Options:
BALANCE
Positive and negative flow components. The positive and negative
flow components are balanced. In other words, net flow in the flow
direction is registered.
FORWARD
Positive flow components only
REVERSE
Negative flow components only
Factory setting:
BALANCE
Totalizer 1 -
Reset
AUTO - OOS Resets totalizer 1 (Totalizer 1 - System Value parameter, see
Page 149) to zero.
Options:
NO
YES
Factory setting:
NO
Note!
Resetting of the totalizer can be also be controlled or initiated using
cyclic data transmission via the Discrete Output function block,
(see Page 181).
TRANSDUCER_TOT (E+H parameters) / base index 1550