PROline Prosonic Flow 93 FOUNDATION Fieldbus 4 Analog Input function block
Endress+Hauser 179
SIMULATE AUTO - MAN -
OOS
Simulation of the input value and input status. Since this value runs
through the entire algorithm, the behaviour of the Analog Input
function block can be checked.
Factory setting:
Simulation Disabled (simulation not active)
Note!
• The BLOCK_ERR parameter of the Resource Block indicates
whether simulation is possible, (see Page 92).
• The BLOCK_ERR parameter of the Analog Input function block
indicates whether simulation is active, (see Page 170).
• The simulation mode is enabled by means of jumpers on the I/O
board, (see Operating Instructions for PROline Prosonic Flow 93
FOUNDATION Fieldbus, BA078D/06/en).
ST_REV read only Displays the revision status of the static data.
Note!
The revision status parameter is incremented on each modification
of static data.
STATUS_
OPTS
OOS Specifies the options for status processing and processing of the
output value OUT.
The following options are supported by the Analog Input function
block:
Options:
Uncertain if MAN mode:
The status of the output value OUT changes to UNCERTAIN if the
operating mode is set to "MAN".
Propagate Fault Forward:
Fault is forwarded on. The status of the corresponding Transducer
Block is relayed to the downstream function blocks via the
BKCAL_OUT parameter.
Factory setting:
No options active
STRATEGY AUTO - MAN -
OOS
Parameter for grouping and thus faster evaluation of blocks.
Grouping is carried out by entering the same numerical value in the
STRATEGY parameter of each individual block.
Factory setting:
0
Note!
These data are neither checked nor processed by the Analog Input
function block.
Analog Input function block /
Base index: AI 1 = 350, AI 2 = 390, AI 3 = 430, AI 4 = 470, AI 5 = 510, AI 6 = 550, AI 7 = 590, AI 8 = 630
Parameter Write access
with operating
mode
(MODE_BLK)
Description