PROline Prosonic Flow 93 FOUNDATION Fieldbus 5 Discrete Output function block
Endress+Hauser 189
SIMULATE_D AUTO - MAN -
OOS - CAS -
RCAS
Simulation of the value and status of the process variable PV_D.
Factory setting:
Simulation Disabled (simulation not active)
Note!
• During the simulation, the value of OUT_D is not passed on to
the Transducer Block. The Transducer Block keeps the last
valid value from before the simulation was activated.
• The BLOCK_ERROR parameter of the Resource Block
indicates whether simulation is possible.
SP_D AUTO - MAN -
OOS
Entry of the discrete setpoint value.
Options:
0 = Starting point, no effect
1 = Reserved
2 = Positive zero return channel 1 "ON"
3 = Positive zero return channel 1 "OFF"
4 = Zero point adjustment channel 1
5 = Reserved
6 = Reserved
7 = Reset totalizers 1, 2, 3
8 = Reset totalizer 1
9 = Reset totalizer 2
10 = Reset totalizer 3
11 = Reserved
12 = Reserved
13 = Reserved
14 = Reserved
15 = Reserved
16 = Positive zero return channel 2 "ON"
17 = Positive zero return channel 2 "OFF"
18 = Zero point adjustment channel 2
ST_REV read only Displays the revision status of the static data.
Note!
The revision status parameter is incremented on each
modification of static data.
STATUS_
OPTS
OOS Selects the available status options for specifying the status
processing and processing of the output value OUT_D.
The following options are supported:
Options:
Propagate Fault Backward
Pass on fault operation to upstream blocks.
Factory setting:
No option active
Discrete Output function block / base index 780
Parameter Write access
with operating
mode
(MODE_BLK)
Description