PROline Prosonic Flow 93 FOUNDATION Fieldbus 6 PID function block (PID controller)
Endress+Hauser 205
FF_VAL ROUT - RCAS -
CAS - AUTO -
MAN - OOS
For displaying and entering the value and status of the
disturbance variable.
User input:
Range and unit of FF_SCALE
GAIN ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Entry of the proportional gain factor.
Factory setting:
0
Note!
If the value 0 is specified for this parameter then the status of the
OUT parameter changes to BAD.
GRANT_
DENY
ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Releases or restricts the access authorisation of a fieldbus host
system to the field device.
Note!
This parameter is not evaluated by PROline Prosonic Flow 93 FF.
HI_ALM ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Alarm status display for the upper warning limit value, (HI_LIM),
including details of the time of the alarm (date, time) and the
value that triggered the alarm.
Note!
In addition, the active alarm can be acknowledged in this
parameter group.
HI_HI_ALM ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Alarm status display for the upper alarm limit value, (HI_HI_LIM),
including details of the time of the alarm (date, time) and the
value that triggered the alarm.
Note!
In addition, the active alarm can be acknowledged
in this parameter group.
HI_HI_LIM ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Entry of the alarm limit value for the upper alarm, (HI_HI_ALM). If
the value PV exceeds this limit value then the alarm status
parameter HI_HI_ALM is output.
User input:
Range and unit of PV_SCALE
Factory setting:
3402823466 x 10
38
Note!
If the setting for the end of the scale is changed in the PV_SCALE
parameter this value should be modified accordingly.
PID function block (PID controller) / base index 810
Parameter Write access
with operating
mode
(MODE_BLK)
Description