6 PID function block (PID controller) PROline Prosonic Flow 93 FOUNDATION Fieldbus
206 Endress+Hauser
HI_HI_PRI ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Specifies the action taken when the upper alarm limit value
(HI_HI_LIM) is exceeded.
User input:
0
The violation of the upper alarm limit value is not evaluated.
1
No notification if the upper alarm limit value is violated.
2
Reserved for block alarms.
3-7
The violation of the upper alarm limit value is output as a user
notice with the appropriate priority (3 = low priority, 7 = high
priority).
8-15
The violation of the upper alarm limit value is output as a critical
alarm with the appropriate priority (8 = low priority, 15 = high
priority).
Factory setting:
0
HI_LIM ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Entry of the alarm limit value for the upper warning (HI_ALM). If
the value PV exceeds this limit value then the alarm status
parameter HI_ALM is output.
User input:
Range and unit of PV_SCALE
Factory setting:
3402823466 x 10
38
Note!
If the setting for the end of the scale is changed in the PV_SCALE
parameter this value should be modified accordingly.
PID function block (PID controller) / base index 810
Parameter Write access
with operating
mode
(MODE_BLK)
Description