PROline Prosonic Flow 93 FOUNDATION Fieldbus 6 PID function block (PID controller)
Endress+Hauser 211
OUT MAN - OOS Displays the output value (manipulated variable) of the PID
function block. The output value contains the value, the limit
value status, the status and the alarm evaluation.
The output value OUT is a function of the OUT_HI_LIM and
OUT_LO_LIM range limit values. If the calculated manipulated
variable exceeds or undershoots the range limit values then the
value of the range limit value in question is output as the output
value OUT, (see diagram).
Note!
If MAN (manual intervention by the operator) is selected for the
operating mode in the MODE_BLK parameter then the output
value OUT can be specified manually here. The unit used is
copied from the OUT_SCALE parameter group, the input area
corresponds to OUT_SCALE ±10%.
OUT_HI_LIM ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Entry of the maximum permissible analog manipulated variable
that can be output from the PID function block.
User input:
Range and unit of OUT_SCALE ±10%
Factory setting:
100
OUT_LO_LIM ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Entry of the minimum permissible analog manipulated variable
that can be output from the PID function block.
User input:
Range and unit of OUT_SCALE ±10%
Factory setting:
0
PID function block (PID controller) / base index 810
Parameter Write access
with operating
mode
(MODE_BLK)
Description
F06-53xFFxxx-05-xx-xx-en-005