6 PID function block (PID controller) PROline Prosonic Flow 93 FOUNDATION Fieldbus
212 Endress+Hauser
OUT_SCALE OOS Definition of the measuring range (lower and upper limit), the
physical unit and the number of decimal places for the
manipulated variable (OUT).
Factory setting:
0...100%
Note!
The range limits are defined via the OUT_HI_LIM and
OU_LO_LIM parameters .
PV read only Displays the process variable used for the block execution,
including the status.
Note!
The unit used is copied from the PV_SCALE parameter group.
PV_FTIME ROUT - RCAS -
CAS - AUTO -
MAN - OOS
Entry of the filter time constant (in seconds) of the digital filter of
the 1st order. This time is required in order for 63% of a change in
the controlled variable at input IN to have an effect on the value
of PV.
The diagram shows the signal curves between the parameters IN
and PV over time:
a) The IN parameter changes.
b) The PV parameter has reacted 63% to the change in the
IN parameter.
Factory setting:
0 s
PID function block (PID controller) / base index 810
Parameter Write access
with operating
mode
(MODE_BLK)
Description
F06-53xFFxxx-05-xx-xx-en-006