GE Power Management 745 Transformer Management Relay 6-9
6 ACTUAL VALUES 6.3 A2 METERING
6
6.3.6 VOLTAGE
6.3.7 DEMAND
The 745 measures current demand on each phase of each monitored winding. These parameters can be mon-
itored to reduce supplier demand penalties or for statistical metering purposes. Demand is calculated based on
the measurement type in
S2 SYSTEM SETUP/DEMAND METERING
. For each quantity, the 745 displays the demand
over the most recent demand time interval, the maximum demand since the last date that the demand data
was reset, and the time and date stamp of this maximum value.
a) DEMAND DATA CLEAR
y VOLTAGE
y [ENTER] for more
This message indicates the start of the Voltage actual values. To view these
actual values press or press for the next section.
SYSTEM LINE-TO-LINE
VOLTAGE: 0.00 kV
This message displays the system’s line-to-line voltage. For phase-to-
neutral input voltages, this display is converted to its line-to-line equivalent.
VOLTS-PER-HERTZ:
0.00 V/Hz
This message displays the calculated volts-per-hertz.
LINE-NTRL VOLTAGE:
0.00 kV at 0°Lag
This message displays the line-to-neutral phase voltage magnitude and
angle.
y DEMAND
y [ENTER] for more
This message indicates the start of the Demand actual values. To view these
actual values press or press for the next section.
y DEMAND DATA CLEAR
y [ENTER] for more
This message indicates the start of the Demand Data Clear actual values. To
view these actual values press or press for the next section.
CLEAR MAX DEMAND
DATA? No
Enter
Yes
to clear all maximum demand data.
DATE OF LAST CLEAR:
Jan 01 1996
This message displays the last date that the demand data was cleared. If the
date has never been programmed, this message will display
Jan 01 1996
.
TIME OF LAST CLEAR:
00:00:00.000
This message displays the last time that the demand data was cleared.
ENTER
MESSAGE
ENTER
MESSAGE
ENTER
MESSAGE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE 745 TRANSFORMER MANAGEMENT RELAY and is the answer not in the manual?

GE 745 TRANSFORMER MANAGEMENT RELAY Specifications

General IconGeneral
BrandGE
Model745 TRANSFORMER MANAGEMENT RELAY
CategoryRelays
LanguageEnglish

Related product manuals