EasyManuals Logo
Home>GE>Relays>745 TRANSFORMER MANAGEMENT RELAY

GE 745 TRANSFORMER MANAGEMENT RELAY User Manual

GE 745 TRANSFORMER MANAGEMENT RELAY
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #59 background imageLoading...
Page #59 background image
GE Power Management 745 Transformer Management Relay 5-9
5 SETPOINTS 5.2 AUTO-CONFIGURATION
5
As shown in the ‘Y/d30
°
’ entry of the table of transformer types, the phase angle correction (or phase shift)
introduces 30
°
lag in Winding 1. This lag is described in Table 5–2: PHASE SHIFTS on page 5–23. This table
provides the following information about each phase shift type:
5.2.6 ZERO-SEQUENCE COMPONENT REMOVAL
1. If zero-sequence current can flow into and out of one transformer winding (e.g. a grounded Wye or zig-zag
winding) but not the other winding (e.g. a Delta winding), external ground faults will cause the differential
element to operate incorrectly. Traditionally, this problem is solved by Delta connecting the CTs on the Wye
side of a Wye/Delta transformer so that the currents coming to the relay are both phase corrected and void
of zero-sequence current. Because the 745 software mimics the CT Delta connection, the zero-sequence
current is automatically removed from all Wye or zig-zag winding currents of transformers having at least
one delta winding.
2. External ground faults also cause maloperation of the differential element for transformers having an in-
zone grounding bank on the Delta side (and the Wye connected CTs on the same side). Traditionally, this
problem is solved by inserting a zero-sequence current trap in the CT circuitry. The 745 automatically
removes zero-sequence current from all Delta winding currents when calculating differential current.
Where there is no source of zero-sequence current (e.g. Delta windings not having a grounding bank), the
745 effectively removes nothing.
3. Autotransformers have an internal tertiary winding to provide a path for third-harmonic currents and control
transient overvoltages. Also, many two-winding Wye/Wye transformers have a three-legged core construc-
tion that forces zero-sequence flux into the transformer tank, creating an inherent Delta circuit. In both
these cases, there is zero-sequence impedance between the primary and secondary windings. The 745
removes zero-sequence current from all windings of Wye/Wye and Wye/Wye/Wye transformers to prevent
possible relay maloperations resulting from these two conditions.
PHASE
SHIFT
INPUT
PHASORS
OUTPUT
PHASORS
PHASOR
TRANSFORMATION
30° lag a = (A – C) /
√
3
b = (B – A) /
√
3
c = (C – B) /
√
3
the phasors after the phase shift is applies (a/b/c/)
the phasors before the phase shift is applied (A/B/C)
the phase shift as it appears in the table of transformer types
the equations used to achieve the
phase shift (A/B/C → a/b/c)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE 745 TRANSFORMER MANAGEMENT RELAY and is the answer not in the manual?

GE 745 TRANSFORMER MANAGEMENT RELAY Specifications

General IconGeneral
BrandGE
Model745 TRANSFORMER MANAGEMENT RELAY
CategoryRelays
LanguageEnglish

Related product manuals