8-26 745 Transformer Management Relay GE Power Management
8.3 MODBUS MEMORY MAP 8 COMMUNICATIONS
8
10TH
HARMONIC
0360 Winding 1 Phase A 10th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0361 Winding 1 Phase B 10th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0362 Winding 1 Phase C 10th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0363 Winding 2 Phase A 10th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0364 Winding 2 Phase B 10th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0365 Winding 2 Phase C 10th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0366 Winding 3 Phase A 10th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0367 Winding 3 Phase B 10th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0368 Winding 3 Phase C 10th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0369 Reserved
↓↓
↓↓
036F Reserved
11TH
HARMONIC
0370 Winding 1 Phase A 11th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0371 Winding 1 Phase B 11th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0372 Winding 1 Phase C 11th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0373 Winding 2 Phase A 11th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0374 Winding 2 Phase B 11th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0375 Winding 2 Phase C 11th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0376 Winding 3 Phase A 11th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0377 Winding 3 Phase B 11th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0378 Winding 3 Phase C 11th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0379 Reserved
↓↓
↓↓
037F Reserved
12TH
HARMONIC
0380 Winding 1 Phase A 12th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0381 Winding 1 Phase B 12th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0382 Winding 1 Phase C 12th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0383 Winding 2 Phase A 12th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0384 Winding 2 Phase B 12th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0385 Winding 2 Phase C 12th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0386 Winding 3 Phase A 12th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0387 Winding 3 Phase B 12th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0388 Winding 3 Phase C 12th Harmonic Content 0.0 to 99.9 0.1 % ƒo F2 ---
0389 Reserved
↓↓
↓↓
038F Reserved
Table 8–6: 745 MEMORY MAP (Sheet 10 of 57)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS FORMAT
CODE
FACTORY
DEFAULT

Table of Contents