8-34 745 Transformer Management Relay GE Power Management
8.3 MODBUS MEMORY MAP 8 COMMUNICATIONS
8
EVENT
RECORDER
DATA
continued
084F Event XX Winding 2 Phase B 5th Harmonic 0.0 to 99.9 0.1 % ƒo F2 0% ƒo
0850 Event XX Winding 2 Phase C 5th Harmonic 0.0 to 99.9 0.1 % ƒo F2 0% ƒo
0851
Event XX Winding 3 Phase A Current Magnitude
--- --- A F80 0 A
0852 Event XX Winding 3 Phase A Current Angle 0 to 359 1 ° Lag F1 0° Lag
0853
Event XX Winding 3 Phase B Current Magnitude
--- --- A F80 0 A
0854 Event XX Winding 3 Phase B Current Angle 0 to 359 1 ° Lag F1 0° Lag
0855
Event XX Winding 3 Phase C Current Magnitude
--- --- A F80 0 A
0856 Event XX Winding 3 Phase C Current Angle 0 to 359 1 ° Lag F1 0° Lag
0857
Event XX Winding 3 Ground Current Magnitude
--- --- A F83 0 A
0858 Event XX Winding 3 Ground Current Angle 0 to 359 1 ° Lag F1 0° Lag
0859 Event XX Winding 3 Phase A 2nd Harmonic 0.0 to 99.9 0.1 % ƒo F2 0% ƒo
085A Event XX Winding 3 Phase B 2nd Harmonic 0.0 to 99.9 0.1 % ƒo F2 0% ƒo
085B Event XX Winding 3 Phase C 2nd Harmonic 0.0 to 99.9 0.1 % ƒo F2 0% ƒo
085C Event XX Winding 3 Phase A 5th Harmonic 0.0 to 99.9 0.1 % ƒo F2 0% ƒo
085D Event XX Winding 3 Phase B 5th Harmonic 0.0 to 99.9 0.1 % ƒo F2 0% ƒo
085E Event XX Winding 3 Phase C 5th Harmonic 0.0 to 99.9 0.1 % ƒo F2 0% ƒo
085F Event XX Phase A Differential Current 0.00 to 655.35 0.01
×
CT F3 0.00
×
CT
0860 Event XX Phase B Differential Current 0.00 to 655.35 0.01
×
CT F3 0.00
×
CT
0861 Event XX Phase C Differential Current 0.00 to 655.35 0.01
×
CT F3 0.00
×
CT
0862 Event XX Phase A Restraint Current 0.00 to 655.35 0.01
×
CT F3 0.00
×
CT
0863 Event XX Phase B Restraint Current 0.00 to 655.35 0.01
×
CT F3 0.00
×
CT
0864 Event XX Phase C Restraint Current 0.00 to 655.35 0.01
×
CT F3 0.00
×
CT
0865 Event XX System Frequency 0.00 to 99.99 0.01 Hz F3 0.00 Hz
0866 Event XX Frequency Decay Rate –9.99 to 9.99 0.01 Hz/s F6 0.00 Hz/s
0867 Event XX Tap Changer Position 1 to 50 1 --- F1 0 = n/a
0868 Event XX Volts-per-Hertz 0.00 to 4.00 0.01 V/Hz F3 0.00 V/Hz
0869 Event XX Ambient Temperature –51 to 251 1 °C F4 0 °C
086A Event XX Analog Input 0 to 65000 1
<Units>
F1 0 <Units>
086B Reserved
↓↓
↓↓
0FFF Reserved
Common Setpoints (Addresses 1000 to 1FFF) - Read / Write
745 SETUP 1000 745 Setpoints --- --- --- F29
0 = Not Prog’d
1001
Encrypted Passcode (4 registers) [read only]
--- --- --- F33 "AIKFBAIK"
1005 Beeper --- --- --- F30 1 = Enabled
1006 Flash Message Time 0.5 to 10.0 0.5 s F2 40 = 4.0 s
1007 Default Message Timeout 10 to 900 1 s F1 300 s
1008 Default Message Intensity 0 to 100 25 % F1 25%
Table 8–6: 745 MEMORY MAP (Sheet 18 of 57)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS FORMAT
CODE
FACTORY
DEFAULT