EasyManua.ls Logo

GE 745 TRANSFORMER MANAGEMENT RELAY - Page 260

GE 745 TRANSFORMER MANAGEMENT RELAY
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-50 745 Transformer Management Relay GE Power Management
8.3 MODBUS MEMORY MAP 8 COMMUNICATIONS
8
SIMULATION
FAULT VALUES
continued
1E47 Fault Winding 3 Ground Current Angle 0 to 359 1 ° Lag F1 0° Lag
1E48 Fault Voltage Input Magnitude 0.0 to 2.0 0.1
×
VT F2 10 = 1.0
×
VT
1E49 Fault Voltage Input Angle 0 to 359 1 ° Lag F1 Lag
1E4A Fault Frequency 45.00 to 60.00 0.01 Hz F3 60.00 Hz
1E4B Reserved
↓↓
↓↓
1FFF Reserved
Setpoint Group 1/2/3/4 (Addresses 2000 to 3FFF) - Read / Write
PERCENT
DIFFERENTIAL
2000 Percent Differential Function --- --- --- F30 1 = Enabled
2001 Percent Differential Target --- --- --- F46 1 = Latched
2002 Percent Differential Pickup 0.05 to 1.00 0.01
×
CT F3 30 = 0.30
×
CT
2003 Percent Differential Slope 1 15 to 100 1 % F1 25%
2004 Percent Differential Break Point 1.0 to 20.0 0.1
×
CT F2 20 = 2.0
×
CT
2005 Percent Differential Slope 2 50 to 200 1 % F1 100%
2006 Percent Differential Block --- --- --- F87 0 = Disabled
2007 Reserved
HARMONIC
INHIBIT
2008 Harmonic Inhibit Function --- --- --- F30 1 = Enabled
2009 Harmonic Inhibit Parameters --- --- --- F64 0 = 2nd
200A Harmonic Averaging --- --- --- F30 0 = Disabled
200B Harmonic Inhibit Level 0.1 to 65.0 0.1 % ƒo F2
200 = 20.0% ƒ
o
200C Reserved
ENERGIZATION
INHIBIT
200D Energization Inhibit Function --- --- --- F30 1 = Enabled
200E Energization Inhibit Parameters --- --- --- F64 0 = 2nd
200F Harmonic Averaging --- --- --- F30 1 = Enabled
2010 Energization Inhibit Level 0.1 to 65.0 0.1 % ƒo F2
200 = 20.0% ƒ
o
2011 Energization Inhibit Duration 0.05 to 600.00 0.01 s F1 10 = 0.10 s
2012 Energization Sensing By Current --- --- --- F30 1 = Enabled
2013 Minimum Energization Current 0.10 to 0.50 0.01
×
CT F3 10 = 0.10
×
CT
2014 Energization Sensing By Voltage --- --- --- F30 0 = Disabled
2015 Minimum Energization Voltage 0.50 to 0.99 0.01
×
VT F3 85 = 0.85
×
VT
2016 Breakers Are Open Signal --- --- --- F88 0 = Disabled
2017 Parallel Transformer Breaker Close Signal --- --- --- F88 0 = Disabled
2018 Reserved
5TH
HARMONIC
INHIBIT
2019 5th Harmonic Inhibit Function --- --- --- F30 0 = Disabled
201A Harmonic Averaging --- --- --- F30 0 = Disabled
201B 5th Harmonic Inhibit Level 0.1 to 65.0 0.1 % ƒo F2
100 = 10.0% ƒ
o
201C Reserved
↓↓
↓↓
Table 8–6: 745 MEMORY MAP (Sheet 34 of 57)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS FORMAT
CODE
FACTORY
DEFAULT

Table of Contents

Related product manuals