8-68 745 Transformer Management Relay GE Power Management
8.3 MODBUS MEMORY MAP 8 COMMUNICATIONS
8
SOFTWARE
DIAGNOSTICS
5030 Unexpected Interrupt Counter 0 to 65535 1 --- F1 0
5031 Last Unexpected Interrupt Vector 0 to 255 1 --- F1 0
5032 Unexpected Reset Counter 0 to 65535 1 --- F1 0
5033 Last Unexpected Reset Cause 0 to 255 1 --- F1 0
5034 EEPROM Scrub Counter 0 to 65535 1 --- F1 0
5035 A/D Virtual Ground Error Counter 0 to 65535 1 --- F1 0
5036 Front RS232 Error Counter 0 to 65535 1 --- F1 0
5037 COM1 Error Counter 0 to 65535 1 --- F1 0
5038 COM2 Error Counter 0 to 65535 1 --- F1 0
5039 Processor Usage 0.0 to 100.0 0.1 % F2 ---
503A RAM Memory Usage 0.0 to 100.0 0.1 % F2 ---
503B Reserved
↓↓ ↓
↓↓↓ ↓
503F Reserved
COMPILE
DATE/TIME
5040 Boot Program Compile Date (2 registers) --- --- --- F23 ---
5042 Boot Program Compile Time (2 registers) --- --- --- F22 ---
5044 Main Program Compile Date (2 registers) --- --- --- F23 ---
5046 Main Program Compile Time (2 registers) --- --- --- F22 ---
5048 Reserved
↓↓ ↓
↓↓↓ ↓
50FF Reserved
CALIBRATION
DATA
5100 Date of Last Calibration (2 registers) --- --- --- F23 ---
5102 Date of Original Calibration (2 registers) --- --- --- F23 ---
5104 x8 to x1 Saturation Level 0 to 32767 1 counts F1 3000 counts
5105 Winding 1 Phase A Current x1 Offset –100 to +100 1 --- F4 0
5106 Winding 1 Phase A Current x1 Gain 0 to 20000 1 --- F1 15556
5107 Winding 1 Phase A Current x8 Offset –100 to +100 1 --- F4 0
5108 Winding 1 Phase A Current x8 Gain 0 to 20000 1 --- F1 15556
5109 Winding 1 Phase B Current x1 Offset –100 to +100 1 --- F4 0
510A Winding 1 Phase B Current x1 Gain 0 to 20000 1 --- F1 15556
510B Winding 1 Phase B Current x8 Offset –100 to +100 1 --- F4 0
510C Winding 1 Phase B Current x8 Gain 0 to 20000 1 --- F1 15556
510D Winding 1 Phase C Current x1 Offset –100 to +100 1 --- F4 0
510E Winding 1 Phase C Current x1 Gain 0 to 20000 1 --- F1 15556
510F Winding 1 Phase C Current x8 Offset –100 to +100 1 --- F4 0
5110 Winding 1 Phase C Current x8 Gain 0 to 20000 1 --- F1 15556
5111 Winding 1/2 Ground Current x1 Offset –100 to +100 1 --- F4 0
5112 Winding 1/2 Ground Current x1 Gain 0 to 20000 1 --- F1 15556
Table 8–6: 745 MEMORY MAP (Sheet 52 of 57)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS FORMAT
CODE
FACTORY
DEFAULT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE 745 TRANSFORMER MANAGEMENT RELAY and is the answer not in the manual?

GE 745 TRANSFORMER MANAGEMENT RELAY Specifications

General IconGeneral
BrandGE
Model745 TRANSFORMER MANAGEMENT RELAY
CategoryRelays
LanguageEnglish

Related product manuals