GE Power Management 745 Transformer Management Relay 8-99
8.5 POINT LISTS
8
28 148 F79 Winding 2 Positive Sequence Current Magnitude Class 1 Note 7
29 149 F80 Winding 3 Positive Sequence Current Magnitude Class 1 Notes 5,8
30 150 F78 Winding 1 Negative Sequence Current Magnitude Class 1 Note 6
31 151 F79 Winding 2 Negative Sequence Current Magnitude Class 1 Note 7
32 152 F80 Winding 3 Negative Sequence Current Magnitude Class 1 Notes 5,8
33 153 F78 Winding 1 Zero Sequence Current Magnitude Class 1 Note 6
34 154 F79 Winding 2 Zero Sequence Current Magnitude Class 1 Note 7
35 155 F80 Winding 3 Zero Sequence Current Magnitude Class 1 Notes 5,8
36 156 F3 Phase A Differential Current Magnitude Class 1
37 157 F3 Phase B Differential Current Magnitude Class 1
38 158 F3 Phase C Differential Current Magnitude Class 1
39 159 F53 Winding 1 Ground Differential Current Class 1 Note 5
40 160 F53 Winding 2 Ground Differential Current Class 1 Note 5
41 161 F53 Winding 3 Ground Differential Current Class 1 Note 5
42 162 F2 Winding 1 Phase A Total Harmonic Distortion Class 1
43 163 F2 Winding 1 Phase B Total Harmonic Distortion Class 1
44 164 F2 Winding 1 Phase C Total Harmonic Distortion Class 1
45 165 F2 Winding 2 Phase A Total Harmonic Distortion Class 1
46 166 F2 Winding 2 Phase B Total Harmonic Distortion Class 1
47 167 F2 Winding 2 Phase C Total Harmonic Distortion Class 1
48 168 F2 Winding 3 Phase A Total Harmonic Distortion Class 1 Note 5
49 169 F2 Winding 3 Phase B Total Harmonic Distortion Class 1 Note 5
50 170 F2 Winding 3 Phase C Total Harmonic Distortion Class 1 Note 5
51 171 F3 System Frequency Class 1 Note 3
52 172 F1 Tap Changer Position Class 1
53 173 F3 System Line-To-Line Voltage Class 1 Note 5
54 174 F3 Volts-Per-Hertz Class 1 Note 5
55 175 F3 Line-To-Neutral Voltage Magnitude Class 1 Note 5
56 176 F4 Ambient Temperature Class 1 Note 5
57 177 F4 Hottest-Spot Winding Temperature Class 1 Note 5
58 178 F2 Insulation Aging Factor Class 1 Note 5
59 179 F7 Total Accumulated Loss Of Life (Note 12) Class 1 Note 5
60 180 F1 Analog Input Class 1 Note 5
61 181 F93 Winding 1 Real Power Class 1 Notes 5,6
62 182 F93 Winding 1 Reactive Power Class 1 Notes 5,6
63 183 F93 Winding 1 Apparent Power Class 1 Notes 5,6
64 184 F3 Winding 1 Power Factor Class 1 Note 5
65 185 F94 Winding 2 Real Power Class 1 Notes 5,7
66 186 F94 Winding 2 Reactive Power Class 1 Notes 5,7
POINT LIST FOR: ANALOG INPUT (OBJECT 30)
ANALOG INPUT CHANGE (OBJECT 32) (Continued)
(Note 5) Index when
Point Mapping Is:
Format Description Event Class
Assigned To
Notes
Disabled Enabled

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE 745 TRANSFORMER MANAGEMENT RELAY and is the answer not in the manual?

GE 745 TRANSFORMER MANAGEMENT RELAY Specifications

General IconGeneral
BrandGE
Model745 TRANSFORMER MANAGEMENT RELAY
CategoryRelays
LanguageEnglish

Related product manuals