11-8 745 Transformer Management Relay GE Power Management
11.1 COMMISSIONING SUMMARY 11 SETPOINT TABLES
11
W1 Phase Inst O/C 1 Block Disabled
W2 Phase Inst O/C 1 Function Enabled
W2 Phase Inst O/C 1 Target Latched
W2 Phase Inst O/C 1 Pickup 10.00 x CT
W2 Phase Inst O/C 1 Delay 0 ms
W2 Phase Inst O/C 1 Block Disabled
W3 Phase Inst O/C 1 Function Enabled
W3 Phase Inst O/C 1 Target Latched
W3 Phase Inst O/C 1 Pickup 10.00 x CT
W3 Phase Inst O/C 1 Delay 0 ms
W3 Phase Inst O/C 1 Block Disabled
W1 Phase Inst O/C 2 Function Enabled
W1 Phase Inst O/C 2 Target Latched
W1 Phase Inst O/C 2 Pickup 10.00 x CT
W1 Phase Inst O/C 2 Delay 0 ms
W1 Phase Inst O/C 2 Block Disabled
W2 Phase Inst O/C 2 Function Enabled
W2 Phase Inst O/C 2 Target Latched
W2 Phase Inst O/C 2 Pickup 10.00 x CT
W2 Phase Inst O/C 2 Delay 0 ms
W2 Phase Inst O/C 2 Block Disabled
W3 Phase Inst O/C 2 Function Enabled
W3 Phase Inst O/C 2 Target Latched
W3 Phase Inst O/C 2 Pickup 10.00 x CT
W3 Phase Inst O/C 2 Delay 0 ms
W3 Phase Inst O/C 2 Block Disabled
NEUTRAL OVERCURRENT
W1 Ntrl Time O/C Function Enabled
W1 Ntrl Time O/C Target Latched
W1 Ntrl Time O/C Pickup 0.85 x CT
W1 Ntrl Time O/C Shape Ext Inverse
W1 Ntrl Time O/C Multiplier 1.00
W1 Ntrl Time O/C Reset Linear
W1 Ntrl Time O/C Block Disabled
W2 Ntrl Time O/C Function Disabled
Table 11–6: S4 ELEMENTS (Sheet 3 of 12)
DESCRIPTION DEFAULT GROUP 1 GROUP 2 GROUP 3 GROUP 4