AT600 User’s Manual 115
Chapter 5. Communication
Command 191 (0xBF): Test Digital Output (cont.)
Table 91: Response Data Bytes for Test Digital Output
Byte Format Description
0 Unsigned-8 Channel Number(1/2)
1 Unsigned-8 Test DO Type
Test Stop
Pulse
Frequency
Alarm;
2 - 5 Unsigned-32 Test value
Table 92:
Command-Specific Response Codes for Test Digital Output
Code Class Description
0 Success No Command-Specific Errors
1Undefined
2 Error Invalid Selection
3-4 Undefined
5 Error Too Few Data Bytes Received
6 Error Device-Specific Command Error
7Error In Write Protect Mode
8-15 Undefined
16 Error Access Restricted
8-127 Undefined