AT600 User’s Manual 133
Chapter 5. Communication
Command 216 (0xD8): Write Calibration Configuration
This command is to write Calibration Configuration.
Table 144: Request Data Bytes for Write Calibration Configuration
Byte Format Description
0 Unsigned-8 Reynolds correction: 0: Disable, 1: Enable
1 Unsigned-8 Active MultiK Enable: 0: Disable, 1: Enable
2 Unsigned-8 KFactor Type:
0: Velocity, 1: Reynolds
3 – 6 Float Static KFactor
7 Unsigned-8 KFactor Points
8 - 11 Float Kinematic Viscosity
Table 145: Response Data Bytes for Write Calibration Configuration
Byte Format Description
0 Unsigned-8 Reynolds correction
1 Unsigned-8 Active MultiK Enable
2 Unsigned-8 KFactor Type:
0: Velocity, 1: Reynolds
3 – 6 Float Static KFactor
7 Unsigned-8 KFactor Points
8 - 11 Float Kinematic Viscosity
Table 146: Command-Specific Response Codes for Write Calibration Configuration
Code Class Description
0 Success No Command-Specific Errors
1-4 Undefined
5 Error Too Few Data Bytes Received
6 Error Device-Specific Command Error
7Error In Write Protect Mode
8-15 Undefined
16 Error Access Restricted
17-127 Undefined