NetworX Version 3 Installation Manual
211
Table 30. Reporting syntax
Format key Description
> The message opening character.
aaaaaa A six-digit account code.
ee A two-digit SIA code.
nnn A three-digit number, e.g. zone number.
Rin Partition modifier, 'Ri' is literal, n is the partition number.
. The message closing character.
/ Separator
[X] X is optional
[X …] X is optional and may be repeated one or more times.
The settings and events in Table 31 are transmitted in the following messages.
>123456 BA001 BA003.
• >987654 YT000.
• >345678 TA030.
Table 31. Example settings and events
Setting Value
System account code for the given destination 987654
Partition 1 account code 123456
Partition 3 account code 345678
BA on zone 1 Partition 1
BA on zone 3 Partition 1
Low battery on panel YT000
TA on zone 30 Partition 3
Combined events
Account codes are used to identify partitions. Events for separate accounts codes can be sent in the
same message using the syntax:
aaaaaa eennn [eennn …][/aaaaaa eennn [eennn …]…].
See
Table 30 for a detailed syntax description.
The settings and events in
Table 31 are transmitted in the following message.
>123456 BA001 BA003/987654 YT000/345678 TA030.