F 6217 (0606)
290
Time const. input filter approx. 10 ms
Basic error 0.1 % at 25 °C
Operating error 0.3 % at 0...+60 °C
Error limit related on safety 1 %
Electric strength 200 V against GND
Space requirement 4 SU
Operating data 5 VDC / 80 mA, 24 VDC / 50 mA
Figure 2: Lead marking cable plug
The module contains a redundant, safety-related processor system. Because of this, all the
tests are executed directly on the module. The main test routines are:
– Linearity of the A/D converters
– Overflow of the A/D converters
– Cross talking between the eight input channels
– Function of the input filters
– Function of the I/O bus communication
Cable
LiYCY
20 x 0.25 mm
2
screened
l = 120 mm
q = 2.5 mm
2
Channel Connection Color
1z4
x4
d4
BN
WH
2z8
x8
d8
YE
GN
3z12
x12
d12
PK
GY
4z16
x16
d16
RD
BU
5z20
x20
d20
VT
BK
6z24
x24
d24
WHGN
WHBN
7z28
x28
d28
WHGY
WHYE
8z32
x32
d32
WHBU
WHPK
L–
L+
d26
d30
BK
RD
Cable screen YEGN
l = 750 mm
q = 1 mm
2
Flat pin
plug 2.8 x
0.8 mm
2
Channel Connection Color
1z4
x4
d4
BN
WH
2z8
x8
d8
YE
GN
3z12
x12
d12
PK
GY
4z16
x16
d16
RD
BU
5z20
x20
d20
VT
BK
6z24
x24
d24
WHGN
WHBN
7z28
x28
d28
WHGY
WHYE
8z32
x32
d32
WHBU
WHPK
L–
L+
d26
d30
BK
RD
Cable screen YEGN
Flat pin plug 6.3 x 0.8 mm, to be connected to the earth bar under the slot
Lead marking cable plug to connect current/
voltage Z 7127 / 6217 / C.. / I (U5V)
Lead marking cable plug to connect voltage via
potentiometer and smart transmitters
Z 7127 / 6217 / C.. / U10V