Data Sheets
49
10.12.3 Digital Output Modules
SU = spacing units (width)
10.12.4 Analog Output Modules
SU = spacing units (width)
24
VDC
> 24 V
safety-
related
SIL 3
Line
Control
Load
Space
require-
ment
Type
Chan-
nels
Slot
detec-
tion
•≤ 0.5 A 4 SU F 3322 16 •
only with
F 6221
•
Transmitter
supply (Ex)i
≤ 22 V, ≤ 60 mA
4 SU F 3325 6 -
•• ≤ 0.5 A 4 SU F 3330 8 •
•••≤ 0.5 A 4 SU F 3331 8 •
•≤ 2 A 4 SU F 3332 4 •
•• ≤ 2 A 4 SU F 3333 4 •
•••≤ 2 A 4 SU F 3334 4 •
• (Ex)i
≤ 24 V, 12 mA
4 SU F 3335 4 •
•• ≤ 0.5 A, 48 V 4 SU F 3348 8 •
••• • ≤ 0.5 A,
24 V or 48 V
4 SU F 3349 8 •
•≤ 4 A, ≤ 60 V 4 SU F 3422 8 •
•• ≤ 4 A,
≤ 110 VDC,
≤ 250 VAC
4 SU F 3430 4 •
Table 9: Digital Output Modules
24
VDC
> 24 V
safety-
related
SIL 3
Line
Control
Load
Space
require-
ment
Type
Chan-
nels
Slot
detec-
tion
• 0...20 mA 4 SU F 6705 2 •
0...20 mA 4 SU F 6706 2 •
Table 10: Analog Output Modules