F 6217 (0606)
294
Figure 9: Lead marking cable plug with transmitter supply
Cable plugs marked with R1 and R2 are for redundant systems, applications refer to previous
figures.
If using the transmitter Saab/Rosemount 3300 GWR with internal zener diode a galvanic iso-
lation in the signal connection must be provided to remove interferences (signal spikes, unde-
fined signal levels) at the analog inputs of the F 6217.
Therefore e.g. the analog isolator with HART
H 6200 of HIMA can be used.
Channel Connection Color
1z4
x4
d4
BN
WH
GN
2z8
x8
d8
GY
YE
PK
3z12
x12
d12
RD
BU
BK
4z16
x16
d16
WHBN
VT
WHGN
5z20
x20
d20
WHGY
WHYE
WHPK
6z24
x24
d24
WHRD
WHBU
WHBK
7z28
x28
d28
BNYE
BNGN
BNGY
8z32
x32
d32
BNBU
BNPK
BNRD
L–
EL+(L+)
d26
d30
BK
RD
Cable screen YEGN
Cable
LiYCY
24 x 0.14 mm
2
screened
l = 120 mm
q = 2.5 mm
2
l = 750 mm
q = 1 mm
2
Flat pin
plug
2.8 x 0.8 mm
2
Flat pin plug 6.3 x 0.8 mm, to be connected to the earth bar under the slot
Lead marking cable plug with transmitter supply Z 7128 / 6217 / C.. / ITI