F 6706 (0507)
338
Line length max. 1000 m (observe burden)
Electric strength 250 V against Analog GND
Basis status at
plug-in I
≤ 20 μA
Source voltage U
Q
(sink mode) 10...30 V
Space requirement 4 SU
Operating data 5 VDC / 40 mA,
24 VDC / 100 mA
Figure 2: Lead marking cable plug
Channel Connection Color
1b8
b6
b4
b10
WH
BN
PK
GY
2b24
b22
b20
b26
GN
YE
RD
BU
L–
L+
b28
b32
BK
RD
Cable screen YEGN
Cable
LiYCY
8 x 0.5 mm
2
l = 120 mm
q = 2.5 mm
2
l = 750 mm
q = 1 mm
2
Flat pin
plug
2.8 x 0.8 mm
2
Flat pin plug 6.3 x 0.8 mm (of the cable screen), to be connected to the
earth bar under the slot
Lead marking cable plug Z 7126 / 6706 / C..
Note: To avoid failures of the module unused channels must be terminated by the
bridge
b6 - b8 for channel 1 or
b22 - b24 for channel 2