5-9
MAN0448_Issue 13_ 01-2010 5704 Control System
005704-M-5001 A03249
CHAPTER 5 - COMMISSIONING AND
MAINTENANCE INSTRUCTIONS
96 No Vps.
Vps is a voltage which is used to set the
absolute value reference for the reading scaling
factor.
The no Vps message is only displayed on
a channel card that has not been factory
tested.
This is a serious card failure and, as such, the
card needs to be replaced.
95 Not used.
94 Not used.
93 CongurationFault
The congurationfaultmessageisdisplayed
during start-up if the channel card has no
congurationinformationortheconguration
is not valid..
This is a serious card failure and, as such, the
card needs to be replaced.
92 Not used.
91 Power Fail Error
The power fail error message is displayed if the
system supply voltage falls below approximately
16V dc.
The error latches* if the power failure delay is
not enabled.
Check the operation of the power supply. When
the power is restored, check the operation of the
system.
All Non Yes Yes
Active
All Non Yes Yes
Active
1V5 Non Yes No
Active
1V6 Non Yes Conf*
or Active
later
Error Error Code Meaning Software Card Fault Latch
Code Version Status Signal