102 IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Programming Point
5880
(input 41-48)
SWITCH MANUAL PULL Refer to comments column of Table 8.6 on page 103 for description of
these options.
Latch or Non-latching feature only appears for WATERFLOW, FIRE
SUPERVISORY, FIRE TAMPER, ZONE AUX1, ZONE AUX2, SYSTEM
AUX1, SYSTEM AUX2, ECS INPUT, ECS TAMPER, and ECS
SUPERVISORY.
WATERFLOW
FIRE SUPERVISORY
FIRE TAMPER
FIRE DRILL
SILENCE
RESET
P.A.S. ACK
ZONE AUX1
ZONE AUX2
SYSTEM AUX1
SYSTEM AUX2
MANUAL RELEASE
INTERLOCK
STATUS POINT
5880
(input 41-48)
SWITCH ECS INPUT User also has ECS Event Number 1-8 option for ECS INPUT, ECS
TAMPER, and ECS SUPERVISORY functions in both 5880 and ECS-VCM
or ECS-NVCM/ECS-RVM choices, when installed in the system.
ECS TAMPER
ECS SUPERVISORY
5496 UNUSED
B NOTIF NOTIF OUTPUT supervised
not supervised
CONTROL CIRCUIT
A NOTIF NOTIF OUTPUT
CONTROL CIRCUIT
AUX_PWR CONSTANT
AUX RESET
AUX DOOR
AUX SYNC Cannot be supervised
5865 UNUSED
NOTIF NOTIF OUTPUT
CONTROL CIRCUIT
ECS Amps UNUSED
NOTIF
Choices Type Selections
Function Selections for
each Type
Comments
Table 8.5 Point Programming Options