IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022 17
Section 3: Prerequisites for Installation
This section of the manual is intended to help you plan your tasks to facilitate a smooth installation. Please read this section thoroughly, espe-
cially if you are installing an IFP-300 panel for the first time.
3.1 Inventory
When an IFP-300 shipment is received, check that all the parts have been included in the shipment. The shipment consist of one of each of
the following:
main circuit board with display
backbox with door.
plastic bag containing two keys, screws, cables, and ten 4.7k ohm end-of-line resistors.
manual
3.2 Environmental Specifications
It is important to protect the IFP-300 control panel from water. To prevent water damage, the following conditions should be followed when
you install the units:
Mount indoors in dry locations only
Do not mount directly on exterior walls, especially masonry walls (condensation)
Do not mount directly on exterior walls below grade (condensation)
Protect from plumbing leaks
Protect from splash caused by sprinkler system inspection ports
Do not mount in areas with humidity-generating equipment (such as dryers, production machinery)
When selecting a location to mount the IFP-300 control panel, the unit should be mounted where it will NOT be exposed to temperatures
outside the range of 32°F-120°F (0°C-49°C) or humidity outside the range of 10%-93% at 86°F (30°C) non-condensing.
3.3 Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades
to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that
you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any
questions about software and the appropriate version for a specific application. Software updates can be found at www.farenhyt.com
3.4 Electrical Specifications
Table 3.1 lists the terminal block on the IFP-300 and a description of the each individual terminal and their respective electrical rating.
Terminal No.
Label
Description
Rating
Group Individual Voltage Current
Terminal Block 1 TELCO 1 RING Phone Line 1 Telco Ring
TIP Phone Line 1 Telco Tip
PHONE 1 RING Phone Line 1 Phone Ring
TIP Phone Line 1 Phone Tip
TELCO 2 RING Phone Line 2 Telco Ring
TIP Phone Line 2 Telco Tip
PHONE 2 RING Phone Line 2 Phone Ring
TIP Phone Line 2 Phone Tip
Terminal Block 2 SLC IN Used for Class A installations 32 VDC 150 mA
+
SLC OUT SLC terminals 32 VDC 150 mA
+
SLC PROG Used for programming SLC
Detectors
32 VDC 150 mA
+
Terminal Block 3 SBUS Out B SBUS Communication 5 VDC 100 mA
A
+ SBUS Power 24 VDC 1.0 A
Terminal Block 4 BATTERY + To Positive battery terminal 24 VDC Up to 35 Ah (See Section 4.5 for details.)
To Negative battery terminal
Table 3.1 Terminal Descriptions and Electrical Specifications

Table of Contents

Other manuals for Honeywell Farenhyt Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt Series and is the answer not in the manual?

Honeywell Farenhyt Series Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt Series
CategoryControl Panel
LanguageEnglish

Related product manuals