IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022 133
Function Keys System Operation
9.8.3 Erasing an F-Key Macro
1. If an F-Key macro has already been recorded, you can erase it by accessing the F-Key Recording menu and selecting the ‘Erase FKEY
Macro option.
2. The panel will return to the Idle screen.
9.8.4 Using a Recorded F-Key Macro
1. From the Idle screen on any annunciator in the site, press the F-Key you want to activate.
2. Once finished, to de-activate the macro press the F-Key again.
9.8.5 F-Key Status Event
When an F-Key is enabled, it activates its corresponding F-Key Active event. This is a status type event that can activate outputs without
showing any status on annunciator displays. This should be used for ancillary purposes only.
9.8.6 F-Key Map Inhibit
The F-Keys have the ability to disable event - output group mapping for the purpose of simulating that the map doesn’t exist. This can be
setup to allow for testing purposes where notification of an entire building is not desired during the test. This option is programmable for
each output group map through HFSS Honeywell Fire Software Suite.
When an F-Key is active and a map in the system is set to be disable by Map Inhibit, the system will show a trouble event indicating it as
such.

Table of Contents

Other manuals for Honeywell Farenhyt Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt Series and is the answer not in the manual?

Honeywell Farenhyt Series Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt Series
CategoryControl Panel
LanguageEnglish

Related product manuals