IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022 73
Voice Options Network Management
5. Press * to add rows, Press ENTER to edit data.
6.3 Voice Options
6.3.1 Edit Timers
1. Login to the panel. The panel will automatically access the Main Menu.
2. Select 6 for Network Programming.
3. Select 7 for Voice Options.
4. Choose Site.
5. Select 1 for Edit Timers
Control Lockout
The Control Lockout countdown timer is set to the programmed value when an LOC gains ECS Control. The timer starts over upon any key
press at the ECS Control LOC. While the Control Lockout timer is active, an LOC of equal priority must request ECS control. The Control
Lockout timer is cleared when ECS Control is relinquished. The Control Lockout Timer does not apply to ECS Super User control.
• Select Immediate/Timer/Never
• Range 0-720 min/0-59 sec
Auto Reset ECS MIC Triggered Event
If you select the Timer, the Event will automatically reset after being active for the programmed time. If Event Disabled is selected, the event
will not be allowed to be activated from an LOC Station. Selecting Never will require an Emergency System Reset to be performed to reset
the event.
Select Never/Timer/Event Disabled, Range from 1-240 min.
6.3.2 Edit Voice Commands
When a voice output group is selected to be activated by a zone, the cadence pattern choice does not apply. For voice output groups, one of
six system wide voice commands will activate instead of the cadence pattern.
1. Login to the panel. The panel will automatically access the Main Menu.
2. Select 6 for Network Programming Menu.
3. Select 7 for Voice Options.
4. Choose Site.
5. Select 2 for Edit Voice Commands.
6. Select the command you wish to edit:
Figure 6.1 Communicator Reporting
P# ASTP Primary.... Test Secondary... Test
01:=03 YYYY R009:321456 N R013:987456 N
02:=02 NNYN R015:123456 N R014:654321 N
* =Add Row
primary receiver number
primary account number
panel number
secondary account number
secondary receiver number
panel number
report alarms
report supervisories
report event by point (Y=point, N=zone)
report troubles
test primary
account
test secondary account
ECS Timer Option
Control Lockout Immediate/Timer/Never
Auto Reset ECS MIC Triggered Event Never/Timer/Event Disabled
Auto Reset ECS Event 1 Never/Timer/Event Disabled
Auto Reset ECS Event 2 Never/Timer/Event Disabled
Auto Reset ECS Event 3 Never/Timer/Event Disabled
Auto Reset ECS Event 4 Never/Timer/Event Disabled
Auto Reset ECS Event 5 Never/Timer/Event Disabled
Auto Reset ECS Event 6 Never/Timer/Event Disabled
Auto Reset ECS Event 7 Never/Timer/Event Disabled
Auto Reset ECS Event 8 Never/Timer/Event Disabled
Table 6.1 Auto Reset ECS MIC Triggered Event Timer Menu

Table of Contents

Other manuals for Honeywell Farenhyt Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Farenhyt Series and is the answer not in the manual?

Honeywell Farenhyt Series Specifications

General IconGeneral
BrandHoneywell
ModelFarenhyt Series
CategoryControl Panel
LanguageEnglish

Related product manuals