12 IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Introduction Compatible Products
Other Modules
5824 Serial/Parallel
Printer Interface Module
Allows a printer to be attached for the system for on-site event logging. Four maximum
per system.
5815XL (Rev H or above)
SLC Expander
Allows up to 127 SD devices to be added to the system. The number of 5815XL
modules that can be added to the system is limited only by the maximum number of
SBUS devices. However the maximum point count is limited to 254 per panel. Supports
SD protocol devices only.
6815 SLC Expander Supports System Sensor Devices (IDP or SK) only. Each 6815 supports up to 159 IDP
or SK sensors and 159 IDP or SK modules. Maximum point count is 300 per panel.
RPS-1000 (Rev F or
higher) Intelligent Power
Supply
Provides additional power, six Flexput circuits,
and two Form C relays.
RPS-1000 and 5496 modules can be
used in any combination, up to a total
of 16 on one system.
5496 (Rev F or above)
NAC Expander
Add 4 Notification/Auxiliary power circuits with
each 5496 Intelligent Power Module
RA-2000 Remote LCD
Annunciator
4x 40 Remote LCD annunciator, can be used in any combination, up to a total of 16
devices on one panel.
RA-100 Remote LCD
Annunciator
4 x 20 Remote LCD annunciator, can be used in any combination, up to a total of 16
devices on one panel.
RA-1000 Remote LCD
Annunciator
4 x 20 Remote LCD annunciator, can be used in any combination, up to a total of 16
devices on one panel.
5860TG and 5860TR
Trim Ring Kits
trim ring kits for surface mounting the RA-1000 annunciator. 5860TG is gray; 5860TR is
red.
5865-3 and 5865-4 LED
Annunciator
LED annunciator can display up to 30 LEDs (15
red and 15 yellow). 5865-4 has key switches for
silence and reset, and a system trouble LED.
5865-3, 5865-4, and 5880 can be
used in any combination, up to a total
of eight devices on one panel.
5880 (Rev C or above)
LED I/O Module
Driver for up to 40 LEDs. Interfaces with
customized annunciator boards. In addition the
5880 has eight generic switch input points.
5883 General Purpose
Relay Module
Provides 10 Form C relays. Designed to be driven by the 5880. Up to four, 5883
modules can be used with each 5880 module.
SK-NIC Network Interface Card Refer to LS10172-001SK-E
ECS Modules
ECS-NVCM Network Voice Control Module Refer to the ECS Series Installation
Manual P/N 151455for more
information on these accessories.
ECS-VCM Voice Control Module
ECS-SW24 24 switch expander
ECS-50W 50 watt audio amplifier
ECS125W 125 watt audio amplifier
ECS-CE4 Provides 4 additional audio circuits for the ECS-
50W or ECS-125W.
ECS-RVM Remote Voice Module
ECS-DUAL50W Dual Channel amplifier
ECS-50WBU Backup daughter card
ECS-INT50W 50 wall internal amplifier
ECS-LOC Local Operating Console
Wireless
WIDP-WGI/WSK-WGI Wireless Gateway
Refer to the SWIFT Wireless
Installation Manual
P/N LS10036-000FH-E for more
information on these accessories.
WIDP-PHOTO/WSK-
PHOTO
Wireless Photoelectric Smoke Detector
WIDP-ACCLIMATE
Wireless multi-criteria photoelectric smoke
detector
WIDP-HEAT-ROR/WSK-
HEAT-ROR
Wireless Rate of Rise Heat Detector
WIDP-HEAT/WSK-HEAT Wireless 135° Fixed Heat Detector
WIDP-MONITOR/WSK-
MONITOR
Wireless Addressable Monitor Module
WIDP-RELAY/WSK-
REALY
Wireless Addressable Relay Module
B
210W 6" wireless base
Type of Device Model Description
Table 1.1 IFP-300 Compatible Products (Continued)