150 IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022
Reporting Receivers Compatible with the Control Panel
ECS Alarm # Point Alarm pi Exp. ID QA (EPPP) E -
Emergency #
PPP - Point #
QANNXXEPPP 1 220 +
Emergen
cy #
Exp. ID Point #
ECS Alarm # Point Alarm Restore pi Exp. ID QH (EPPP) E -
Emergency #
PPP - Point #
QHNNXXEPPP 3 220 +
Emergen
cy #
Exp. ID Point #
ECS Alarm # Point Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 242 Exp. ID Point #
ECS Alarm # Point Trouble Restore pi Exp. ID QJ Point # QJNNXXPPPP 3 242 Exp. ID Point #
ECS Alarm # Point Disabled pi Exp. ID QB Point # QBNNXXPPPP 1 243 Exp. ID Point #
ECS Alarm # Point Enabled pi Exp. ID QU Point # QUNNXXPPPP 3 243 Exp. ID Point #
ECS Supervisory/Tamper Alarm pi Exp. ID QS Point # QSNNXXPPPP 1 241 Exp. ID Point #
ECS Supervisory/Tamper Alarm Restore pi Exp. ID QR Point # QRNNXXPPPP 3 241 Exp. ID Point #
ECS Supervisory/Tamper Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 242 Exp. ID Point #
ECS Supervisory/Tamper Trouble Restore pi Exp. ID QJ Point # QJNNXXPPPP 3 242 Exp. ID Point #
ECS Supervisory/Tamper Disabled pi Exp. ID QB Point # QBNNXXPPPP 1 243 Exp. ID Point #
ECS Supervisory/Tamper Enabled pi Exp. ID QU Point # QUNNXXPPPP 3 243 Exp. ID Point #
ECS NAC Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS NAC Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
ECS Control Circuit Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS Control Circuit Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
ECS Relay Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS Relay Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
ECS Notification Trouble pi Exp. ID QT Point # QTNNXXPPPP 1 320 Exp. ID Point #
ECS Notification Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP 3 320 Exp. ID Point #
External Reset/Silence/Fire Drill switch
disabled
pi Exp. ID UB Point # UBNNXXPPPP 1 571 Exp. ID Point #
External Reset/Silence/Fire Drill switch
enabled
pi Exp. ID UU Point # UUNNXXPPPP 3 571 Exp. ID Point #
External Reset/Silence/Fire Drill switch
trouble
pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
External Reset/Silence/Fire Drill switch
trouble restore
pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
Interlock switch alarm (Water Release
Zone)
pi Exp. ID FA Point # FANNXXPPPP 1 110 Exp. ID Point #
Interlock switch alarm restore (Water
Release Zone)
pi Exp. ID FH Point # FHNNXXPPPP 3 110 Exp. ID Point #
Interlock switch disabled pi Exp. ID FB Point # FBNNXXPPPP 1 571 Exp. ID Point #
Interlock switch enabled pi Exp. ID FU Point # FUNNXXPPPP 3 571 Exp. ID Point #
Interlock switch trouble (Water Release
Zone)
pi Exp. ID FT Point # FTNNXXPPPP 1 373 Exp. ID Point #
Interlock switch trouble restore (Water
Release Zone)
pi Exp. ID FJ Point # FJNNXXPPPP 3 373 Exp. ID Point #
LOC Mic Activated ECS Alarm pi Exp. ID QA 0 QANNXX0000 1 220 Exp. ID 000
LOC Mic Activated ECS Alarm Restore pi Exp. ID QH 0 QHNNXX0000 3 220 Exp. ID 000
SIA Reporting Format Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module
ID #
(If Any)
SIA
Event
Code
s
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 11.2 Report Formats Table (Continued)