IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022 85
Programming Menu Quick Reference Programming Overview
Zone Edit Zone Select Zone Edit Zone Name See “Edit Zone
Name” on
page 97.
Zone
Properties
Verification
Type
*1-Count See “Edit Zone
Properties” on
page 97.
2-Count
Alarm Verif.
PAS
SNGL
ILOCK
DBL ILOCK
Heat Temp Set 135° to
150°F
SD devices. See
“Edit Zone
Properties” on
page 97.
135° to
190°F
IDP or SK device.
See “Edit Zone
Properties” on
page 97.
Smoke
Sensitivity
Low See “Edit Zone
Properties” on
page 97.
Medium
High
Zone
Accessory
Opt
Single/Multi-
station Cadence
00-23 See “Zone
Accessory
Options” on
page 99.
CO Single/Multi
station Cadence
00-23
Local Zone Yes
No
View Zone Points Select Zone Section 8.4.2
Group Edit Group Select Group Group Name See “Edit Group
Name” on
page 100.
Group
Properties
Voice Group Y or N See “Edit Group
Properties” on
page 100.
Switch 1-64
Tem plat e
Override
Y or N
Allow Sys
Override
Y or N
Dynamic
Act/Template
Override
Cadence
00-23 See “Edit Group
Properties” on
page 100 and
Appendix C.
View Group Points Select Group Section 8.4.2
Edit OPG
Tem plat e
Select template Modify name and which output groups (OPGs) are in the
template
Section 8.4.3
Menu Options/Defaults Comments
Table 7.4 Programming Menus Quick Reference List (Continued)