IFP-300 Series Manual — P/N LS10145-001SK-E:C 4/6/2022 93
Programming Menu Quick Reference Programming Overview
System
Options
cont.
Communication
Options
AlarmNet Timers Ethernet Supervise 75 sec, 90 Sec,
3 min, 5 min, 1
hr, 24 hrs, 30
days, None
*5 Minutes See “AlarmNet
Timers” on
page 113.
Cellular Supervise 24Hrs, 30 days,
none
*24 Hours
Old Alarm Time 10 min, 15 min,
30 Minutes, 1 hr,
2 hrs, 4 hrs, 8
hrs, 12 hrs,
24hrs, none
*30 Minutes
Phone Line Gains Dialing High *High See “Phone Line
Gains” on
page 114.
Low
Normal
Reporting Low *Low
Normal
High
Daytime/Nighttime
Sensitivity
Enable/Disable Yes *No Section 8.6.2
No
Day Start Enter time *6:00AM
Night Start Enter time *6:00PM
Days of the Week Select days *-MTWTF-
Holiday Days Holidays 1 to 18 Enter dates *01/01,
07/04,
12/24, 12/25
Section 8.6.3
Time Options Water Flow Delay 0 - 90 Seconds *1 sec Section 8.6.4
Alarm Verify 60 to 250 seconds *60 sec
Low AC Report Time 0 - 30 hours *3 hrs
AC Freq: 50 Hz *60Hz
60 Hz
Internal
Clock Display Format AM/PM *AM/PM
MIL
Auto-resound 4 hours *24 hours
24 hours
Miscellaneous
Options
SYNC Strobes when
Silenced
Y *N Section 8.6.5
N
Auto Display Events Y *N
N
Daylight Saving
Options
Auto Daylight Saving Y *Y Section 8.6.6
N
DST Start Select week: 1st, 2nd,
3rd, 4th or Last
Select month Section 8.6.6
DST End
Edit Banner Refer to Appendix A. Section 8.6.7
SLC Family IDP Section 8.6.8
SK
SD
Jump
Start
AutoPrg
Y (Yes) Section 8.7
N (No)
Restore
Defaults
Y (Yes)
N (No)
Section 8.8
Menu Options/Defaults Comments