Revision 6    HC900 Process & Safety Controller User and Installation Manual  99 
21 April 2017 
16 point High Level Analog Input Wiring (Figure 49) 
Be sure to set the module DIP switches for voltage or current mode. See page 87. This requires Low 
Voltage Euro style 36-terminal terminal block. 
Note: Unused input channel shall not be left open for 900A16-0102 IO module 
 
Figure 49 – 16 point High Level Analog Input Wiring 
4 channel Analog Output Module Wiring 
An example of Analog Output Module wiring is shown in Figure 50.  Specifications for this module and for 
other modules are given in the Specifications manual. SIL applications require an external series relay used 
to ensure outputs achieve failsafe action. See HC900 Process & Safety Controller Safety Manual for 
additional details.  
Isolation 
The four outputs are isolated from each other.  
Shield Grounding 
Shields must be grounded as described under Shield Grounding at the beginning of this section. 
   
Hazardous voltages exist at terminal blocks. 
  Using switches at field devices disconnect the field wiring form power sources before servicing.