188    HC900 Process & Safety Controller User and Installation Manual  Revision 6 
    21 April 2017 
I/O Module Diagnostic Indication 
To indicate the type of diagnostic failure, the module’s status LED is flashed red with a number of quick 
strobes followed by a long off time. Table 31 outlines the potential module diagnostics. 
   
Hazardous voltages exist at terminal blocks. 
AO8 and AO16 modules require at least one channel to be configured prior to a cold start for the module 
to work properly. Subsequent channels then may be added with a hot start. 
Failure to comply with these instructions could result in death or serious injury. 
Table 31 – I/O Module LED Diagnostics 
The module is in the failsafe state 
because it is not receiving message 
requests from the CPU or Scanner  
at a rate that satisfies the configured 
failsafe timeout. 
1.  If expansion I/O rack, go to step 2. 
If no expansion I/O rack, go to 
step 3. 
2.  Check the Scanner status LED 
(see  p. 183).  
  If it’s flashing 6 times, proceed 
with step 3.  
  If it’s flashing some other red 
status code, refer to Table 29 
to solve that problem first.  
  If it’s flashing green, the module 
probably is not required in the 
configuration.  
  If it’s not on or steady, cycle 
power to the scanner.  
3.  Make sure the module is the 
correct one for the configuration. 
4.  Remove the module and check 
for a bent pin, then reinsert the 
module 
5.  Replace the module 
6.  Remove other modules and 
replace one at a time until the 
problem reoccurs. Most likely the 
last module inserted needs to be 
replaced. 
7.  Replace the rack. 
EA ROM Failed its checksum 
1.  Remove/reinsert module. 
1.  Remove/reinsert module. 
1.  Remove the module and check 
for a bent pin, then reinsert the 
module 
2.  Measure power supply voltage. If 
not correct, replace power supply. 
3.  Replace module 
4.  Replace rack 
CRC failure of primary and backup 
factory calibration 
CRC failure of field calibration 
values 
1. Remove/reinsert module.