Cable/Wiring Distance Planning 
For all installations observe the following guidelines.  
  Maximum length of RS-232 cabling (Controller to PC) is 50 feet (15.2 meters). 
  Maximum length of RS-485 cabling is 2000 feet (609.6 meters).  
  For Ethernet connections, cable length must be less than 100m. For greater than 100m a switch is 
required. The use of Ethernet cables in excess of 100 meters and/or devices other than recommended 
Switches will cause transmission delays on the I/O link which could have adverse affects on Controller 
performance. 
  You can also use fiber optic cable for connections between the controller and a remote rack.  Please refer 
to HC900 specification document (51-52-03-31) for more details. 
  With redundant CPUs, when using 2 or more I/O racks an Ethernet switch is required between each CPU 
and the I/O racks. Use Honeywell-approved switches only. (see page 215) 
  Maximum of 2 switches between each CPU’s I/O port and all I/O racks. 
  Cable lengths specified in this manual are absolute.  When planning for routing of cables and wires, be 
certain to include vertical and horizontal routing within cabinets, raceways, and conduits. 
  It is advantageous to minimize length of I/O wiring.  However, it is also a good idea to locate racks (and 
wiring) away from adverse environmental conditions such as sources of RFI, EMI, and away from areas 
with high levels of moisture, dust, and corrosive materials.