170    HC900 Process & Safety Controller User and Installation Manual  Revision 6 
    21 April 2017 
Manual Failover 
  Via Key Switch on the Redundancy Switch Module in the Redundant Controller Rack. When doing 
manual failover with keyed switch, turn key to Failover and hold it there until both Reserve lights are 
on, then release the key. 
  Via Software Command from HC Designer & HC Utilities PC Software 
  Via Software Command from Modbus / TCP & Serial Modbus RTU Hosts 
  Via Software Command from 900 Control Station. 
  Via input to RSTAT Function Block to initiate failover  (User can configure logical conditions such as 
loss of communication handshake between Host and Controller to initiate failover). 
Failover Performance 
Failure condition detection and failover from Lead to Reserve CPU executed in 4 analog control cycles or 
less. 
Redundancy Diagnostic Monitoring 
  From HC Designer and HC Utilities PC Software 
 Redundant System Status - current status of Lead/Reserve Controller CPU’s 
 On-Line Monitoring, Controller Diagnostics, Communications Loop-Back tests 
 Redundant Link Status – status of communications between Lead and Reserve controllers. 
 Lead CPU status 
 Reserve CPU status 
 Scanner status 
File Download/Upload Functions 
See page 163.