Revision 6    HC900 Process & Safety Controller User and Installation Manual  27 
21 April 2017 
Power Supply 
The P01 Power Supply, shown in Figure 10, provides 5 Vdc and 24 Vdc to the backplane connectors in the local and 
remote racks.  Power Supply is used in each Controller Rack, I/O expansion racks and for all rack versions (4-slot, 
8-slot, and 12-Slot). 
The lower capacity P02 power supply is available for reduced I/O applications and for Redundant Controller rack 
power. 
P24 power supply provides 5VDC and 24VDC to satisfy the power requirements of a single controller with I/O, a 
Remote I/O rack or a Redundant C75 CPU.  The 60 watt capacity requires minimal de-rating of the available HC900 
I/O modules.  
A tool-secured door covers the voltage connections.  An internal non-replaceable fuse limits supply current under 
certain fault conditions.  
Each power supply includes an internal 5.0-amp fuse that 
is not field-replaceable.  (An external fuse may be added 
by the user. See page 25) 
Items shown with key numbers: 
1.  Voltage test points (P01model only) 
2.  AC/DC Input terminal block 
3.  Wiring label 
4.  Grounding lug (Reference; lug is not part of Power 
Supply; it is staked to bottom of Rack.) 
 
 
 
 
Figure 10 – Power Supply