Revision 6    HC900 Process & Safety Controller User and Installation Manual  81 
21 April 2017 
Signal Grounding ( 
Figure 39) 
The shield for each input should be grounded 
at the grounding bar (optional) at the top or 
bottom of each rack as indicated in Figure 40.  
For low-frequency noise rejection, I/O wiring 
shields should be grounded only at the 
controller end.   
For high-frequency noise rejection, shields 
should be grounded at the controller and at 
the field device. If the ground voltage 
potential at the field device is different from 
that at the controller, a DC isolation capacitor 
should be used between the shield and the 
grounding bar on the rack.  
 
 
 
 
Figure 39 – Signal-Wire Grounding 
 
Aluminum grounding bars for I/O wiring are available as options.  When selected for use, they are fastened 
to the top and/or bottom of each rack, as indicated in Figure 40.  To enable connection of multiple ground 
wires with a single screw, the wires can be twisted together and secured with a wire lug. 
To facilitate module replacement, it is advisable in most cases to route all wiring through either the top or 
the bottom of the terminal block.  This 
allows the terminal block to pivot up or 
down, allowing ready access to the 
module, and is the preferred method 
for a limited number of wires.   
For a larger number of wires, or for 
wires of a heavier gauge, it is advisable 
to route some wires through the top of 
the terminal block, and some through 
the bottom, as indicated in Figure 40.  
In this case, it is necessary to adjust 
wire length so as to ensure adequate 
flexibility of the twisted wires and to 
provide clearance sufficient to remove 
the I/O module.  
 
Figure 40 – Wire-Shield Grounding