176    HC900 Process & Safety Controller User and Installation Manual  Revision 6 
    21 April 2017 
Controller Status LED Diagnostic indicators 
When the Controller has a flashing amber status LED after power-up a critical, power-on-self-test, error has 
occurred that requires controller module replacement. When the Controller Status LED (Figure 89 on page 174, item 
1) is flashing red, consult Table 27. 
   
Hazardous voltages exist in the equipment enclosure. 
  Identify and avoid contact with voltage sources. 
  Disconnect power before servicing.  (More than one switch may be required to disconnect all power.) 
Failure to comply with these instructions could result in death or serious injury. 
Table 27 – Controller Status LED Diagnostics 
Lead and/or Reserve Controller 
Action(s) 
HCDesigner/HC 
Utilities Indication 
RAM or ROM failed on 
power-up. 
Executes an infinite loop that toggles 
the LED. Communications and 
control are disabled. 
2.  Replace CPU 
3.  Replace power supply 
4.  Replace rack 
5.  Check grounding 
6.  Ensure system is properly isolated 
from noise 
Not available 
because the C75 
communication 
ports are disabled. 
Not available 
because the C75 
communication 
ports are disabled. 
At least one function 
block has an output 
that is forced. 
The block’s output(s) is/are forced to 
the value(s) specified. 
If it is not desirable to have forced 
block outputs, use HCDesigner to 
locate and remove the forced outputs. 
See SYSTEM in 
the “Controller 
Diagnostics 
Overview” display. 
See System 
Diagnostics in 
the “Diagnostic 
Overview” dialog 
box. 
The RAM and FLASH 
copies of the 
configuration database 
were corrupted and 
are now set to a valid 
empty database. 
Usually this is a result 
of a firmware upgrade. 
An empty database is created, and 
the lead and reserve will not 
synchronize. The reserve’s RSM 
LED is flashing to indicate it’s not 
synchronized with the lead. 
Use HCDesigner, HCUtilities, or OI to 
download a valid configuration. 
One of the following 
RSM failures was 
detected: 
1.  The RSM module is 
not installed. 
2.  The RSM switch 
position is invalid. 
3.  The lead and 
reserve switch 
positions do not 
agree. 
The lead uses its own switch 
reading and dictates to the reserve 
what the mode is. If the lead’s switch 
position is invalid, then the lead uses 
the last good known position prior to 
the failure. 
If failover occurs, the new lead will 
assume the mode prior to failover 
until a good switch reading is 
acquired. 
If after the power is cycled to both 
the lead and reserve, and the lead is 
unable to acquire a valid switch 
position, the system will default to 
the run-program mode of operation. 
This diagnostic will cause the 
HWOK pins of the analog and fast 
logic “System Monitor” blocks 
(AYSY and FSYS) to be turned off. 
1. Install RSM if none present. NOTE: 
WHEN PLUGGING IN THE RSM 
INTO A LIVE UNIT, YOU MUST 
MAKE SURE THE SWITCH IS IN 
THE PROPER STATE PRIOR TO 
INSERTION. 
2. If the key is installed in the RSM, 
remove it to make sure the switch is 
seated properly. If the key does not 
pull out, turn it slightly to the proper 
position until it can be removed. 
3. Replace the RSM 
4. Replace reserve CPU 
5. Replace lead CPU 
6. Replace rack