48    HC900 Process & Safety Controller User and Installation Manual  Revision 6 
    21 April 2017 
DC Power Supply 
The P24 DC power supply is for use with +24V input power applications. The wattage rating is the same as 
the P01, 60W.  
Rack Orientation and Mounting 
Racks must be mounted as indicated in illustrations throughout this manual, so as to provide for vertical 
airflow through the racks.  That is, racks must never be mounted vertically, and must never be mounted 
with the backplane horizontal (for example, flat on a horizontal panel or tabletop).  Environmental 
specifications apply only to the normal mounting configuration.  
Rack dimensions, including overall dimensions and patterns for drilling holes for mounting, are given in 
Figure 24 and Figure 25.  Vertical spacing of racks, which is required for rack ventilation and for routing 
wires, is shown in Figure 26.   
 
Figure 24 – Rack Dimensions