74    HC900 Process & Safety Controller User and Installation Manual  Revision 6 
    21 April 2017 
Assemble I/O Expansion Racks 
I/O Expansion Rack assembly information is given in Table 11. 
Table 11 – Assemble I/O Expansion Racks 
Insert power supply into left-most slot 
in the I/O rack. See Table 9 steps 1 
and 2 for wiring details.  
If using redundant power, your I/O rack will contain a second 
smaller compartment, see 1 in the following figure. Insert first 
power supply in the larger compartment as shown, to the 
immediate right of the plate dividing the two compartments. 
Redundant Power (optional): 
Insert the second power supply in the 
left side of the smaller compartment, 
see 1 in figure above. See Table 9 
steps 1 and 2 for details. 
Insert the PSM between the 2 power 
supplies. Fasten it in place with 
screws at top and bottom. 
See 1 in figure above. See Table 9 steps 1 and 2 for wiring 
details.